Quick answer: IEC 60870-5-104 commands use COT 6 (Activation) and are confirmed with COT 7 (Activation Confirmation). Single and double commands (types 45/46) write to Modbus coils (FC05) or holding register bits, while scaled and short-float set-points (types 48/49/50) write to holding registers via FC06 or FC16 in Direct Execute or Select-Before-Operate (SBO) mode.

Control-Direction Type IDs in IEC 60870-5-104 (Types 45–50 & 58–63)

When a SCADA control center sends switching commands or analog setpoints to field equipment through an IEC 104 gateway, it uses control-direction ASDUs with Cause of Transmission COT 6 (Activation). Max IEC Gateway translates those commands directly into Modbus writes:

IEC Type IDTime-Tagged VariantControl Data TypeModbus Write Action
C_SC_NA_1 (45)C_SC_TA_1 (58)Single Command (OFF = 0, ON = 1)FC05 Write Single Coil (0x0000 or 0xFF00) or mapped Holding Register bit
C_DC_NA_1 (46)C_DC_TA_1 (59)Double Command (OFF = 1, ON = 2)FC05 Write Single Coil or 2-bit Holding Register command word
C_SE_NA_1 (48)C_SE_TA_1 (61)Set-Point Command, Normalized (-1.0 .. +1.0)Inverse-scaled and written via FC06 or FC16 to Holding Register(s)
C_SE_NB_1 (49)C_SE_TB_1 (62)Set-Point Command, Scaled Integer (INT16)FC06 Write Single Holding Register
C_SE_NC_1 (50)C_SE_TC_1 (63)Set-Point Command, IEEE-754 Short Float (FLOAT32)FC16 Write Multiple Holding Registers (2 registers in configured byte order ABCD/CDAB/BADC/DCBA)

Direct Execute vs. Select-Before-Operate (SBO)

Every IEC 104 command qualifier byte (QOC / SCO / DCO / QOS) carries a S/E (Select/Execute) bit in bit 7:

  • Direct Execute (S/E = 0): The SCADA master sends a single command with COT = 6 (act) and S/E = 0. The gateway immediately executes the Modbus write (FC05/FC06/FC16), replies with COT = 7 (actcon) positive confirmation once the Modbus slave acknowledges the write, and optionally sends COT = 10 (actterm) termination.
  • Select-Before-Operate (SBO, S/E = 1 then S/E = 0): Required for critical circuit-breaker and substation switching:
    1. Step 1 — Select: Master sends command with S/E = 1 (Select) and COT = 6. The gateway verifies the point exists, is writable, and the downstream Modbus device is online, arms a per-IOA select timer (configurable 1–60 s, default 10 s), and returns COT = 7 (actcon) without writing to Modbus yet.
    2. Step 2 — Execute: Master sends matching command with S/E = 0 (Execute) and COT = 6 before the select timer expires. The gateway performs the Modbus write and responds with COT = 7 (actcon) + optional COT = 10 (actterm).
    3. Cancel / Deactivation: If the operator cancels the command, the master sends COT = 8 (deact); the gateway clears the armed selection and replies with COT = 9 (deactcon).

How Floating-Point Setpoints (C_SE_NC_1, Type 50) Map to Modbus

When a SCADA operator writes a floating-point setpoint such as 400.0 kW active power limit using C_SE_NC_1 (50) or C_SE_TC_1 (63), Max IEC Gateway applies the inverse of the point's scale/offset (Raw = (IEC_Value - Offset) / Scale), encodes the value into the device's configured data type (such as FLOAT32 ABCD, FLOAT32 CDAB, or scaled INT16/INT32), and writes the registers atomically via FC16.

Frequently asked questions

Why does my IEC 104 command return a negative confirmation (P/N bit = 1, COT 7)?

A negative confirmation (P/N = 1) is returned when (1) the target IOA is not mapped to a writable Coil or Holding Register, (2) the point is configured for Select-Before-Operate (SBO) and the master sent Execute without a preceding Select within the SBO timeout, or (3) the downstream Modbus device rejected the write or timed out.

What is COT 10 (Activation Termination) in IEC 104?

After the outstation confirms command activation with COT 7 (actcon), COT 10 (actterm) signals that the command execution sequence has finished. Max IEC Gateway allows enabling or disabling ACT_TERM per your SCADA master's profile.