Quick answer: Max IEC Gateway 1.3.0 includes 9 built-in device templates (Eastron SDM120/SDM630, Schneider PM5xxx/Altivar, Carlo Gavazzi EM24, SMA, SunSpec, Growatt, ABB ACS580) and validated CSV import/export to map float measurements (M_ME_NC_1), kWh energy counters (M_IT_NA_1) and curtailment setpoints (C_SE_NC_1) in minutes.

Pre-Built Modbus-to-IEC 104 Device Templates in Max IEC Gateway v1.2

Instead of typing dozens of register addresses by hand, Max IEC Gateway 1.3.0 includes 9 ready-to-use industrial device templates plus CSV bulk import/export. Below is how common smart meters, solar inverters, and VFDs map from Modbus into IEC 60870-5-104:

Template / EquipmentModbus Function & Data TypesMapped IEC 104 Type IDsTypical Parameters Included
Eastron SDM630 / SDM120FC04 Input Regs · FLOAT32 (ABCD)M_ME_NC_1 (13) / M_ME_TF_1 (36) + M_IT_NA_1 (15)Phase L1/L2/L3 voltages, currents, active/reactive power, PF, frequency & kWh import/export counters.
Schneider PowerLogic PM5xxxFC03 Holding Regs · FLOAT32 (ABCD) & INT64M_ME_NC_1 (13) & M_IT_TB_1 (37)3-phase RMS currents, L-L/L-N voltages, total kW/kVAR/kVA, frequency & accumulated energy.
Carlo Gavazzi EM24FC04 / FC03 · INT32 (CDAB) scaledM_ME_NC_1 (13) & M_IT_NA_1 (15)Grid voltages, phase currents, active power (W), and total kWh counters.
SMA / SunSpec Solar InvertersFC03 · INT16/UINT16/INT32 + scaleM_ME_NC_1 (13), M_SP_NA_1 (1), C_SE_NC_1 (50)AC output power, DC string voltage/current, grid frequency, operating state, and active power curtailment setpoint.
Growatt PV InvertersFC04 Input & FC03 Holding · UINT16/UINT32M_ME_NC_1 (13), M_IT_NA_1 (15), C_SC_NA_1 (45)PV1/PV2 input voltage/power, grid AC output, daily/total kWh yield, and remote ON/OFF control.
Schneider Altivar & ABB ACS580 VFDsFC03 / FC06 · UINT16 & INT16 bitfieldsM_SP_NA_1 (1), M_ME_NB_1 (11), C_SC_NA_1 (45), C_SE_NB_1 (49)Drive status word bits (Ready, Running, Fault), output frequency/current/torque, Start/Stop command & speed reference.

Recommended IOA Range Planning for Multi-Device Substations & PV Plants

When a single Max IEC Gateway polls 10–50 field devices and presents them under a single Common Address (e.g. CA = 1), assign structured Information Object Address (IOA) blocks so SCADA engineers can identify every point immediately:

  • Device 1 (Grid Meter SDM630): Statuses IOA 1001–1099 · Analog Floats IOA 1101–1199 · Energy Counters IOA 1201–1220 · Commands IOA 1301–1320
  • Device 2 (Inverter #1): Statuses IOA 2001–2099 · Analog Floats IOA 2101–2199 · Energy Counters IOA 2201–2220 · Setpoints IOA 2301–2320
  • Device N: Base IOA = N × 1000. Export your first device to CSV, increment the IOA column in Excel, and import all devices in seconds with Max IEC Gateway's validated CSV importer!

Frequently asked questions

Can I import and export point mappings in Excel / CSV?

Yes. Max IEC Gateway 1.3.0 supports CSV export and validated all-or-nothing CSV import with a live preview before applying changes.

Can one gateway poll both Modbus TCP inverters and RS-485 serial meters at the same time?

Yes. You can configure multiple Modbus TCP connections, RS-485/RS-232 serial lines (with multiple RTU slave IDs per serial port), and RTU-over-TCP gateways simultaneously, and serve all of them to up to 10 IEC 104 SCADA masters.

Test IEC 104 commands & telemetry live with Max IEC Gateway

Download the free 30-day trial for Windows 10/11 or Linux x64 and inspect every Modbus poll and IEC 104 ASDU in the live web traffic monitor.

Download Free Trial All IEC 104 Guides